Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What do the indication lights on the Micrologic trip units mean?

Issue:
Trip indicator lights on Micrologic

Product Line:
Circuit Breakers

Resolution:
Ir:
The Ir long-time pickup and delay levels were exceeded.
Isd/ Ii: The Isd short time pickup or the Ii instantaneous pickup was exceeded.
Ig: The Ig ground fault pickup level and delay levels were exceeded.
Ap: The self-protection indicator light lights when the trip unit causes the breaker to trip for a reason other than an overcurrent on the Ir, Ii, Isd, or Ig functions.
The Ap light can indicate:
* issue with internal current sensors, usually moisture or corrosion
* The instantaneous override level is exceeded
* fail-safe protection for the circuit in case of the trip unit malfunction
* trip unit temperature approaches 90°C
* overvoltage on 24 Vdc inputs F1-F2

Related Links
FA176046: Determining the cause of breaker tripping with Ap light indication on the Micrologic trip unit
Instruction Bulletin 48049-136-05:  Micrologic 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units


trip indication lights

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings