Can the 9065 type SF solid state overload relays mount to an 8536 type S starter?

Issue:
Mount a 9065 type SF solid state overload relay to an 8536 type S starter?


Product Line:
NEMA Contactors and Starters


Environment:
8536 Type S Starters


Cause:
Can the 9065 type SF solid state overload relays mount to an 8536 type S starter?


Resolution:
The solid state overload relays from size 00 to size 1 are the same for separate mounting and replacement/retrofit mounting; size 2 and above use the type ST instead of the type SF and these devices are designed for separate mounting, not for mounting to a starter. The 9065 type ST should be used to mount to size 2 and above starters.