Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are my options to have Modbus RTU on a TSX Premium controller?
Issue:
What are my options to have Modbus RTU on a TSX Premium controller?

Product Line:
TSXP57, Premium,

Environment:


Cause:


Resolution:
There are two options for Modbus RTU for the Premium PLC.  There is a RS232 and a RS485 PCMCIA cards.
For RS232 modbus PCMCIA card, the part number is TSXSCP111. There are two cables available for the PCMCIA card, TSXSCPCD1030 (3m) or TSXSCPCD1100 (10m).  The cable has a DB25 on the end.

For RS485 modbus PCMCIA card, the part number is TSXSCP114 .  There are two cables available for the PCMCIA card,TSXSCPCM4030 (3m RS485 2-wire with flying leads on the end) or TSXSCPCM4530 (3m RS485 2-wire or 4-wire with DB15 on the end).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings