Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can a Powerlogic or ION meter be used for monitoring Variable Frequency Drives (VFDs)?
Issue
Can the output of a VFD be measured using a Powerlogic or ION metering solution?

Product Line
Powerlogic Metering
ION Metering

Environment
Metering
Energy Management

Cause
Can ION or Powerlogic meters be used to monitor the output of a VFD for energy consumption and/or frequency monitoring.

Resolution
Powerlogic and ION metering families are not designed for non-sinusoidal variable frequency waveforms. These meters are designed to measure a fairly constant frequency, and have a very small range of variance (usually 45-65 Hz depending on the specific device). Because of this, they are unable to measure the output of a variable frequency drive.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings