Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Errant Time-Stamps on ION8650 meter waveform data
Issue:
Time-stamps from 1969 are seen on the time axis of waveforms on ION8650 meters. These errant time signatures occur only on waveforms that are captured around a power up/down of the meter.

Product Line:
ION8650

Environment:
ION8650 meters on firmware version 409 or earlier that capture waveforms at the power up/down of the meter.

Cause:
The hardware team has investigated this and has confirmed this as a firmware related issue.

Resolution:
Applying firmware version 004.020.001 for the ION 8650 will resolve this issue.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings