Will the JDCMH mounting kit accept 2 pole J frame breakers?
Issue:
JDCMH characteristics

Product Line:
Panelboards

Resolution:
Yes, the JDCMH will accept 2 pole J-frame breakers since the 2 and 3 pole J-frame breakers are the same dimensions.
Conditions for the JDCMH are:
- CDP interior with flat or extruded bus
- Cannot mount an old breaker back to back with new PowerpacT breaker