What is the part number for a 24Vdc coil for an 8536 Type S starter?

Issue:
Availability of a 24Vdc coil for 8536 Starters

Product Line:
Class 8536 Type S NEMA starters

Environment:
US Product

Cause:
24Vdc control is common for IEC style devices

Resolution:
There is no 24Vdc coil for 8536 NEMA starters. If 24Vdc control is desired, use an interposing relay with a 24Vdc coil to control the coil circuit.