Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How many BCPMs can the EGX gateway have downstream?
Issue
What is the maximum number of BCPMs the EGX gateways can have installed downstream?

Product Line
Branch Circuit Power Meter

Environment
BCPM installation

Resolution
EGX Gateways support a maximum of 32 Modbus TCP/IP client connections. Since the BCPM use two modbus addresses it will be able to read up to 16 BCPM units.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings