Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Form R for 9036 float switches - reverse action

Issue:

How can the action of a 9036 float switch be changed so that the contacts open on rise and close on fall?

Product Line:

9036D and 9036G switches:

Environment:

US product

Cause:

Different applications require different contact arrangements

Resolution:

The form code R when added to te end of a 9036D or 9036G part number will reverse the action of a float switch.  The standard action of a float switch is for contacts to close on rise.  A reverse action switch will open on rise.  This modification can be field installed on 9036DG switches only with part 9049A58.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings