Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Where can I find information on the ATV212 Modbus communication, specifically related to the RJ45 and the screw terminals pin outs?

Article available in these languages: Spanish


See the attached file for details.

Pinout on the RJ45 connector
Pin 4= + DB or D1
Pin 5= - DA or D0
Pin 8= com

Definitions of the Screw terminals
B= +, DB or D1
A= - DA, or D0
GND= common
SCR= shield

The complete Modbus manual for the ATV212 products is downloadable from this link: https://www.se.com/us/en/download/document/S1A53844/

**************

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
ATV212 RJ45 and screw terminal connections.pdf [106.1 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings