Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is the undervoltage trip included with time delay units for Powerpact breakers?
Issue:
Does the UVR time delay units include the undervoltage trip device?

Product Line:
Powerpact H, J, L, M, P and R frame molded case circuit breakers

Environment:
Products sold and used in the United States

Cause:
Need time delay for UVR - want to know if just time delay is needed, or time delay + undervoltage trip

Resolution:
The time delay units for Powerpact molded case circuit breakers, both adjustable and non-adjustable, do NOT include the undervoltage trip. Select the UVR separately to meet required control voltage for the circuit.

NOTE: For Powerpact H, J, L - Selecting the correct UVR when a Time Delay Unit is required
The output of the Time Delay Unit contains a large DC component, even when applied on an AC system.
This requires selecting a DC-rated UVR in lieu of an AC-rated UVR. Select as shown below

Table

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings