Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the default energy rollover value for ION meters?
Issue
A user would like to know the default rollover values of the various ION meters.

Product Line
ION meters

Environment
Energy Calculations

Cause
A user would like to know the default rollover values of the various ION meters.

Resolution
Below is a list of ION meters and their default rollover values:

NOTE: By default, some of the meters have a Default Rollover Value of 0. This disables the rollover feature. In this case the meter will continue to accumulate energy until it hits the Maximum Energy Value.
Meter NameDefault Rollover ValueMaximum Energy Value
ACM37100999,999,999
ACM37200999,999,999
ION620010,000,000999,999,999
ION63000999,999,999
ION730010,000,000999,999,999
ION733010,000,000999,999,999
ION735010,000,000999,999,999
ION7500999,999,999
ION755010,000,000999,999,999
ION7600999,999,999
ION765010,000,000999,999,999
ION77000999,999,999
ION83000999,999,999
ION84000999,999,999
ION85000999,999,999
ION860010,000,000999,999,999
ION865010,000,000999,999,999
ION88000999,999,999
PM800010,000,000999,999,999
ION900010,000,000999,999,999

To avoid losing any resolution of the energy accumulate value it is recommend that the roll-over be set to 10 000 000. 16777215 (=2^24-1) is the absolute limit imposed by the 32bit IEEE register format without loss of resolution on the stored number.

NOTE: For instructions on how to change the rollover values on ION meters, please refer to: FA209519

Schneider Electric USA

Explore more
Product:
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings