HAND-OFF-AUTO contact arrangement for 9001KS43 or 9001SKS43
Issue:
What contacts are needed for a standard HAND/OFF/AUTO (HOA) arrangement on a 9001KS43 or 9001SKS43 selector switch?

Product Line:
9001SK/9001K selector switches

Environment:
US Product

Cause:
Selector switches sometimes need contacts added in the field.

Resolution:
For a traditional HAND/OFF/AUTO selector switch function wherein one contact is closed only in the left hand position, no contacts are closed in the middle position, and a second independent contact is closed only in the right hand position, use a 9001KA1 contact block on the back of the 9001KS43/9001SKS43 selector switch.  With this particular switch (which uses a C cam), the NC contact will be closed only in the left hand position (HAND), the NO contact will be closed only in the right hand position (AUTO), and no contacts will be closed in the middle position (OFF).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings