Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: Why I am seeing only 2 components of phasor diagram of my delta connected ION meter in ION Setup's phasor view?
Issue
For a delta connected ION meter, the phasor diagram in ION Setup (ION Setup>Setup Assistant>Verification>Wiring>Phasor Viewer), shows only 2 components: (for voltage) V 12 and V 32, (for current) I1 and I3.

Where are the V23 and I2?

Combined Phasor Viewer
Side by Side Phasor Viewer



Product Line
PM8000, ION7650/7550/7500/7600/73xx/86xx/8500/8400/8300
ION Setup 3.0.x

Environment
ION Setup>Setup Assistant>Verification>Wiring>Phasor Viewer

Cause
ION Setup provides 2 ways to view the phasor diagram for a delta connected ION meter:
Instrument (60 Delta)
System (120 Delta)

Instrument view corresponds to how an electrician wants to see it (are the meter voltage and current inputs correctly wired up) whereas, system view corresponds to how the phasor diagram should look like on the primary side of the measured system.

By default, the instrument view is selected.
Options


Resolution
Please go to the ION Setup menu bar>Tools>Options>Conventions>Delta Vector Display>(change it to)System (120 Delta).



Options
Combined Phasor viewer
Side by Side Phasor Viewer

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings