Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to disable the input phase loss detection on an ATV312 drive?
Issue:
Single phase power and disabling input phase loss.

Product Line:
ATV312

Environment:
Only accessible on 3 phase drives
ATV312H...M3 and ATV312H...N4

Cause:
With single phase power supply, the VFD trips PHF.

Resolution:
Enter and scroll down to FLT-.
Enter and scroll down to IPL.  Set it to no.
Note:  The drive state must not be running.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings