Which measurements are summable by the Hierarchy Manager

Issue
Virtual Meters setup using Hierarchy Manager recognize certain measurements as summable measurements.

Product Line

Power Monitoring Expert 2024

Power Monitoring Expert 2023

Power Monitoring Expert 2022

Power Monitoring Expert 2021

Power Monitoring Expert 9.x

Power Monitoring Expert 8.x

Power Monitoring Expert 7.2.x



Environment
Power Monitoring Expert Software Configuration

Cause
It's important to know which measurements are recognized as "summable" by Hierarchy Manager to understand the information provided by Virtual Meters. This is especially critical in devices which might not use the standard labels, and as such the Hierarchy Manager does not know that it should sum this measurement for the constituent meters.

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

Run the attached SQL script. All measurements returned by this query are "summable". Other measurements are averaged.

Schneider Electric USA

Attachment(s)
HierarchyManagerSum.sql [709 Bytes]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings