Is the Powerpact L frame, 600 A breaker 100% rated?
Issue:
Is the Powerpact L frame, 600 amp breaker 100% rated?

Product Line:
Molded case circuit breakers

Resolution:
No. The 400 A and below L frames are available in 100% and 80% rated. The 600 A L frame is only available in 80% rating. 100% rated options for 600 A breakers are the Powerpact P and R frames, as well as Masterpact NT and NW.