Video: How to change power sign or other parameters in Micrologic 6.0P or 5.0P trip units
Issue:
How to change parameters using the screen on Micrologic P trip units

Product Line:
Micrologic Trip Units

Resolution:


In order to change settings via the menu buttons on the trip unit, the trip unit must be energized AND the door over the adjustment dials MUST be OPEN.
To change the power sign:
  1. Press the Wrench menu button
  2. Select Micrologic Setup
  3. Select Power Sign
  4. Toggle power sign with up or down arrow
  5. Press Enter to select sign
  6. Press Wrench button to exit
  7. Select YES to save settings on exit
See attachment for Power Sign Setup.  To change other parameters, review instruction bulletin 48049-137-05 for the Power trip unit or 48049-330-03 for the Harmonic trip unit

Schneider Electric USA

Attachment(s)
Micro P trip unit CHANGE POWER SIGN 48049-137-05 7-2008.pdf [61.43 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings