Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the Micom Px4x relays be upgraded to meet the new cyber security standards?
Issue
Older firmware of the Micom Px4x relay doesn't have cyber security standard IEC62351.

Product Line
Micom Px4x relays

Environment
Cyber security

Cause
Only hardware versions with part numbers corresponding to L and M support new cybersecurity standards

Resolution
  • Cyber security only runs on CPU3/XCPU3 which corresponds to hardware "L" for Micom 40 TE or "M" for Micom 60 and 80 TE.
  • An older version of the relay would have to be replaced with a new main board embedded in the front panel.
  • A new ethernet board, designed for cyber security + IEC61850 ed 2 +HSR/PRP would also need to be implemented in the relay.
  • Finally, the software version(Firmware) with Cyber security would have to be flashed on the relay.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings