NOR0200 returns 'This point may make Binary_input discontinuity' error.

Issue
NOR0200 returns 'This point may make Binary_input discontinuity' error.

Product Line
BMXNOR0200

Environment
BMXNOR0200

Resolution
If you try to add a point that is not in consecutive order, the following error will get returned.
erty

This is just a warning to inform the user that the new point which was to the 'Data Mapping' web page was not added using a point number
that is in consecutive order.  This can be confirmed by exporting the configuration to a '.xml' file and viewing the file with Wordpad.  It will show
that the point numbers are not in consecutive order.  This does not have an impact on the functionality of the NOR0200 module.

The pop-up warning can be ignored.

The following is extracted from the user manual:

rty

To eliminate the error, use the following steps:

  • Export the configuration to a '.xml' file.
  • Downlaod the 'M340 BMXNOR RTUconf Tool'

http://www.unitypro-experts.us/toolsdownload

  • Install the 'M340 BMXNOR RTUconf Tool'.
  • Open the '.xml' file with the 'M340 BMXNOR RTUconf Tool' (the points are automatically resorted in the consecutive order).
  • Save the xml file as a new file.
  • Imported the new configuration file into the NOR module.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings