How can you set up the ATV21 and ATV212 drives for a 4 to 20mA loss of follower?

Issue:
Setting up the ATV21 and ATV212 drives for a 4 to 20mA loss of follower.

Product Line:
Altivar ATV21 and ATV212 drive.

Environment:
All

Cause:
They want to get the drive to fall back to a fixed speed if the 4 to 20mA signal is loss.

Resolution:
Press MODE and hold the arrow down to F----- and press enter
F633= Loss of VA set to any value above 0%
s
F644= 4-20mA loss behavior
F649=Fallback speed set point in hz.
s
See the programming manual https://www.se.com/us/en/download/document/S1A53838/ for more information.

*******

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings