Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What class of fuse do the QMJ type branch switches use?

Article available in these languages: Spanish

Issue:
Current Design product feature

Product Line:
QMJ Type Fusible Branch Switches

Resolution:
All the QMJ branch switches will ONLY accept class J fuses.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings