Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do you set up the ATV12 drive for 3 wire control?
Issue:
3 wire control setup on an ATV12

Product Line:
Altivar ATV12

Environment:
All

Cause:
He has 2  momentary pushbuttons 1 NC for stop and 1 NO for start

Resolution:
Arrow down to the FULL menu enter
Arrow down to IO menu enter
find tCC enter and set this to 3C ( you will need to hold the enter button for 3 seconds before it will change from 2C to 3C)

Schneider Electric USA

Attachment(s)
Programming manual.pdf [9.6 MB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings