Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
When using more than one ground bar in a QO or Homeline load center, is a jumper wire needed to be connected between the two?
Issue:
Product feature

Product Line:
QO and Homeline Load Center

Resolution:
No jumper wire is required. The ground bars are attached to the load center enclosure with thread forming screws, which will give continuity between the ground bars via the enclosure.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings