Are all NEMA 3R covers for Speed-D and QED switchboards hinged on the same side?
Issue:
Product Features

Product Line:
QED switchboards

Environment:
NEMA PB-2, UL 891, NFPA 70 Art. 408

Cause:
An understanding of this feature can help identify replacement parts, when needed.

Resolution:
A detailed explanation is required:
  • Speed-D NEMA 3R enclosure doors are hinged opposite of QED-2 and S.
  • Speed-D is right hinged, the others left hinged.
  • For a single section 48 inches wide or wider, a double door is used (with hinges on left and right).
  • If a EUSERC metering compartment is one of two adjacent sections, that EUSERC section and the other adjacent section will have a double door (the left section, left-hinged; the right section, right hinged).
  • The 36 inch wide Speed-D NEMA 3R enclosure door and the 36 inch wide QED-S/2 door can be interchanged, effecting a "switch" in the side of the section which is hinged;  however, the hinges must be moved (the portions which are bolted to the frame).
  • The part number for a Speed-D 36 in wide NEMA 3R door is 80370-128-50.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings