Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to program an input on the ATV12 to freewheel stop?
Issue:
Configure an ATV12 to freewheel stop

Product Line:
Altivar 12

Environment:
All serial numbers

Cause:
N/A

Resolution:
To program an input to freewheel stop on the ATV12 use the following steps from RDY:

Press enter to rEf
Turn clockwise to ConF press enter.
Turn clockwise to Full press enter.
Turn clockwise to Fun press enter.
Turn clockwise to Stt- press enter.
Turn clockwise to nSt press enter.
Select the input  to use for nSt press enter.
Esc back to the beginning and cycle power.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings