Selecting Micrologic Device Type in Management Console
Issue
Incorrect selection of Micrologic device type can lead to lag communication and manual configuration of Vista default device diagrams.

Product Line
Software: ION Enterprise, Structureware Power Monitoring, Power Monitoring Expert
Circuit Breakers: Masterpact, Powerpact, Compact NS, Compact NSX

Environment
Applications with breaker communication with Schneider Electric power monitoring software

Cause
Need to select the correct device type for Micrologic circuit breaker

Resolution
The below tables display the correct device type for a given Micrologic trip unit type.
Trip UnitsPME Device Type
Micrologic 2.0No Communications
Micrologic 3.0No Communications
Micrologic 5.0No Communications
Micrologic 2.0 AmmeterMicrologic A or Micrologic A IFE_IFM
Micrologic 3.0 AmmeterMicrologic A or Micrologic A IFE_IFM
Micrologic 5.0 AmmeterMicrologic A or Micrologic A IFE_IFM
Micrologic 6.0 AmmeterMicrologic A or Micrologic A IFE_IFM
Micrologic 7.0 AmmeterMicrologic A or Micrologic A IFE_IFM
Micrologic 2.0 EnergyMicrologic E or Micrologic E IFE_IFM
Micrologic 3.0 EnergyMicrologic E or Micrologic E IFE_IFM
Micrologic 5.0 EnegryMicrologic E or Micrologic E IFE_IFM
Micrologic 6.0 EnergyMicrologic E or Micrologic E IFE_IFM
Micrologic 5.0 PowerMicrologic P or Micrologic P IFE_IFM
Micrologic 6.0 PowerMicrologic P or Micrologic P IFE_IFM
Micrologic 7.0 PowerMicrologic P or Micrologic P IFE_IFM
Micrologic 5.0 HarmonicMicrologic H or Micrologic H IFE_IFM
Micrologic 6.0 HarmonicMicrologic H or Micrologic H IFE_IFM
Micrologic 7.0 HarmonicMicrologic H or Micrologic H IFE_IFM
Trip UnitsPME Device Type
Micrologic 2.2No Communications
Micrologic 2.3No Communications
Micrologic 3.2No Communications
Micrologic 3.3No Communications
Micrologic 5.2 AmmeterMicrologic A Compact NSX
Micrologic 6.2 AmmeterMicrologic A Compact NSX
Micrologic 5.3 AmmeterMicrologic A Compact NSX
Micrologic 6.3 AmmeterMicrologic A Compact NSX
Micrologic 5.2 EnergyMicrologic E Compact NSX
Micrologic 6.2 EnergyMicrologic E Compact NSX
Micrologic 5.3 EnergyMicrologic E Compact NSX
Micrologic 6.3 EnergyMicrologic E Compact NSX

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings