Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to setup plus and minus speed on the ATV212?

Article available in these languages: Spanish


Issue:
Shows how to setup plus and minus speed on the ATV212.

Product Line:
ALTIVAR 212

Environment:
All serial number

Cause:
N/A

Resolution:
Follow these steps to program terminal R for plus speed, and RES for minus speed.
Frequency Mode Select (FNOD) = 5 (+/- speeds)
Logic input R (F112) = 41 (+ speed)
Logic input RES (F113) =42 (- speed)

See ATV212 Programming manual for details.
https://www.se.com/ww/en/download/document/S1A53838/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings