Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How many HEPD80 protection devices are needed for (2) 200A load centers in my home?

Issue:
Are 2 HEPD80 surge protection devices needed for (qty 2) 200A load centers in a residency?

Product Line:
Home Surge Protective Device, Surgelogic

Environment:
Application

Cause:
Clarification

Resolution:
If the Load centers have individual feeds then you will need two HEPD80 SPD units.  If the Load centers are mounted side by side, with one incoming feed, and the 1st Load center has a breaker feeding the other Load center , one SPD in the first load Center is only needed and will provide protection for both of the Load centers .

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings