LC1F Mounting Positions
Issue:
What possible mounting positions can the LC1F Contactors be used in without derating?

Product Line:
LC1F contactors - GIC Product
LC1F115 through LC1F2100

Environment:
US Product

Cause:
Product Characteristics

Resolution:
The LC1F contactors can be mounted in a standard vertical orientation with up to a 30 degree incline forward, or they can be rotated 90 degrees counter-clockwise from a standard vertical with no incline forward or backward.  These are the only acceptable mounting positions without derating.  Please see the attached documentation for additional information.

Schneider Electric USA

Attachment(s)
LC1F Mounting.pdf [153.79 KB]