Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can an ATV212 drive be setup to ignore a com fault and continue running at same speed?

Issue:
Configuring the ATV212 to ignore a communication fault and continue running at the current speed reference

Product Line:
ALTIVAR 212

Resolution:
Set parameter F851 = 1
In case of a network communication loss, the VFD will not go to a fault status, but rather continue with the last commanded operation.  If stopped, it will remain stopped.  If running, it will remain running at the last speed reference given.
Consider safety ramifications for this action.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings