Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What would cause the ATV66 drives to blow the input line fuses on power up?

Issue:
Possible causes for an ATV66 drives to blow the input line fuses on power up.

Product Line:
Altivar ATV66

Resolution:
Before replacing the line fuses and power it back up again, please get a Fluke meter, and do a full diode static check on the input L1 L2 L3 and  U, V, W output terminals to + and - bus.
The full diode check will show you two readings, you will measure .3vdc to .7vdc in forward bias direction or OL in the reverse direction.
Please reference the ATV66 troubleshooting and repair manuals VD0C06S701, and VD0C06S702 for more information on where and how do perform static checks on the drive.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings