Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What can cause an E21 fault on the Altivar ATV21 and ATV212 drives?
Issue:
E21 fault code on ATV21 and ATV212

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Drive powers up with an E21 CPU is failing

Resolution:
The E21 is a CPU error 2 fault.   If you power cycle and the fault does not clear the drive will need to be replaced.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings