Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How do I connect the RPO(Remote Power Off) function If using multiple CL-NA units?

Issue:
How do I connect the RPO (Remote Power Off) function if using multiple CL‑NA units?

Product Line:
Context CL‑NA (multiple CL-unit installations)
This product was discontinued, and equivalent equipment may be selected based on site requirements.

Environment:
Installations using multiple CL units with RPO (Remote Power Off) functionality

Cause:
By default, the unit comes with a shorting link connection if the RPO function is not being used.

Resolution:
If planning to use multiple CL units with RPO functionality, you need to:
-Remove the shorting link from the RPO terminals.
-Daisy-chain the RPO terminals across the CL units as shown in Figure 1.
-Ensure the last device in the daisy chain is connected to an external switch with Normally Closed (NC) contacts (see Figure 1).

Figure 1. RPO (Remote Power Off) connection for single inverter and multiple inverter (daisy-chain) installations.


image
Note: The last device in the daisy chain will be connected to an external switch which has normally closed contacts.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings