How do you change the default display setting on an ATV12 drive?
Issue:
ATV212 default display adjustment

Product line:
ATV12, Altivar 12

Environment:
All

Cause:
n/a

Resolution:
The default display for the ATV12 will show Output Frequency.  To change this, enter into the Monitor menu (NOn).  Select the desired value you would like to see.  Push Enter a second time on that value and it will save your setting.

Some common options are:
rFr - Output Frequency
Frh - Reference Frequency
ULn - Line voltage
LCr - motor current

For further options, please consult the User Manual, document number BBV28581