Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Geo SCADA: What counts as a 'point' towards the point count?

Problem

In Geo SCADA, what counts as a 'point' towards the server license's point count?

Solution

We often receive the question, "what constitutes a point in the Geo SCADA database". As there is a point count limit in the server license, this is a valid question. The answer can be summed up as follows:

  • any driver point (analog, digital, string or time) (i.e. DNP3, modbus, OPC, etc)
  • Calculation points
  • internal points
  • pager points
  • performance monitor points

The following points do not count towards the points limit in the server license:

  • Accumulator points
  • Parameter objects
  • Time Profile objects
  • Value Map objects
  • Variable objects

The screen shot below shows the groups who's points count towards the point count in the license:

image1



If a user is ever not sure whether a point counts towards the point count in the license, a real time update can be seen in the server status as follows:


image2

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings