How to set the IO Board Parameters in Scadapack Workbench?

The module_address parameter defines the module address of the sp5607 I/O module.

The address on the module is selected via dip switches on the module. A maximum of eight SCADAPack 5607 I/O type modules may be added to a system

The ain0_type parameter sets the analog input type for analog input channel 1.

There are four input types available.

  • An ain_type of 0 sets the input type to measure 0 to 5V input signals.
  • An ain_type of 1 sets the input type to measure 0 to 10V input signals.
  • An ain_type of 2 sets the input type to measure 0 to 20mA input signals.
  • An ain_type of 3 sets the input type to measure 4 to 20mA input signals.

The ain_filter Parameters:

  • An ain_filter value of 0 sets the input filter for 3Hz and the response time to 155ms at 60Hz and 185ms at 50Hz.
  • An ain_filter value of 1 sets the input filter for 6Hz and the response time to 85ms at 60Hz and 85ms at 50Hz.
  • An ain_filter value of 2 sets the input filter for 11Hz and the response time to 45ms at 60Hz and 55ms at 50Hz.
  • An ain_filter value of 3 sets the input filter for 30Hz and the response time to 30ms at 60Hz and 30ms at 50Hz.

The scan_freq parameter sets the input scan rate for analog inputs. AC noise rejection is improved at the correct frequency. If the module is used in a DC environment, the 60 Hz setting will yield slightly faster response time.

  • A scan_freq value of 0 synchronizes the input scanning to 60Hz.
  • A scan_freq value of 1 synchronizes the input scanning to 50Hz.

The aout_type parameter sets the analog output type for both optional analog output channels.

  • An aout_type value of 0 sets the output type for 0 to 20mA signals.
  • An aout_type value of 1 sets the output type for 4 to 20mA signals.


Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings