Can fine stranded wire be used in Panelboards , such as RHH wire ?
Issue:
Can fine stranded wire be used in Panelboards , such as RHH wire ?

Product Line:
NQ/NF/I Line /QMB

Environment:
Application

Cause:
Code clarification

Resolution:
Wire specifications for Panelboards are found in the NEC.  It is up to the installer to determine the correct wire for the application, and they must follow NEC guidelines.

NEC 110.14 states "Connectors and terminations for conductors more finely stranded than Class B and Class C stranding as shown in Chapter 9, Table 10,  shall be identified for the specific conductor class or classes."

Also, per UL Standard 486 A-B, a terminal/lug/connector must be listed and marked for use with conductors stranded in other than Class B. With no marking or factory instructions to the contrary, terminals may be used only with Class B stranded conductors.
NOTE:
See the Attached NEMA document regarding the use of fine stranded conductors

Schneider Electric USA

Attachment(s)
Bull_105_Fine-Stranded Connections.pdf [107.05 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings