Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to change query name (measure name) in dashboard?
Issue
How to change query name (measure name) in dashboard

Product Line
Power Monitoring Expert 8.0

Envrionment
SQL Server management Studio

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

Here are the steps you can change the measurement name on Dashboard to what you want to display (take Block Demand Apparent Power Total as example)
1.  Open SQL Management Studio and connect ot the PME instance
2.  Find ResourceKeyId in Internationalization.LocalizedString in ApplicationModules database, such as
SELECT *  FROM [ApplicationModules].[Internationalization].[LocalizedString]  where value = 'block demand apparent power total'
3.  Change the Value from "Block Demand Apparent Power Total" to "kVA Total"
4.  Refresh Web Application and you will see the new measurement name.

Screen capture can be found in attachment (Screen Capture).

Schneider Electric USA

Attachment(s)
Screen_Capture.png [24.56 KB]
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings