Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
ATV212 unshielded cable length without motor choke is not provided in catalog, please provide clear information on maximum cable length allowed to use with ATV212 ?
Regarding the clarification related to ATV212 motor cable length, below are the validated information after the tests and validation process at factory,

For reference ATV212H075N4 to ATV212HD15N4:
***********************************************************
1- Maximum cable length for shielded motor cable, with and without filter (motor choke or additional EMC filter) The cable length for this configuration is 25m without motor choke and 100m with motor choke (without EMC compliance). The cable length for this configuration is 20m without filter (with EMC compliance Category C3).
2- Maximum cable length for un-shielded motor cable, with and without filter (motor choke or additional EMC filter). The cable length for this configuration is 50m without motor choke and 150m with motor choke (without EMC compliance).

For reference ATV212HD18N4 to ATV212HD45N4:
***********************************************************
1- Maximum cable length for shielded motor cable, with and without filter (motor choke or additional EMC filter) The cable length for this configuration is 25m without motor choke and 150m with motor choke (without EMC compliance). The cable length for this configuration is 20m without filter (with EMC compliance Category C3).
2- Maximum cable length for un-shielded motor cable, with and without filter (motor choke or additional EMC filter). The cable length for this configuration is 50m without motor choke and 300m with motor choke (without EMC compliance).

For ATV212HD55N4 and ATV212HD75N4:
*************************************************
1- Maximum cable length for shielded motor cable, with and without filter (motor choke or additional EMC filter) The cable length for this configuration is 25m without motor choke and 150m with motor choke (without EMC compliance). The cable length for this configuration is 20m without filter (with EMC compliance Category C3).
2- Maximum cable length for un-shielded motor cable, with and without filter (motor choke or additional EMC filter). The cable length for this configuration is 50m without motor choke and 300m with motor choke (without EMC compliance).

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings