Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Event Notification Module 8.3 with Power Monitoring Expert 8.0 alarms not coming into the monitoring section

Issue
Event Notification Module 8.3 not bringing in Alarms from Power Monitoring Expert 8.0

Product Line
Power Monitoring Expert 8.0
Event Notification Module 8.3

Environment
Monitoring and Diagnostics web interface

Cause
Issue with the Alarms.ENMAlarms.dll in the .../system/bin folder of Power Monitoring Expert

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

  1. Replace the Alarms.ENMAlarms.dll in the .../system/bin with the one from the attached Hotfix.
  2. Restart the ENM services by clicking Start -> run -> services.msc

The Services are:
PL Alarm Sentry Host Service
SE Event Gathering Service
SE Event Notification Service
SE Event Logging Service

Schneider Electric USA

Attachment(s)
Hotfix_47138.7z [8.48 KB]
Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings