Product Line
PM8000
ION Setup

Environment
ION Setup

Cause
User would like to:

  • clear all the accumulated energy values and custom device quantities
  • clear meter logged data, events, and waveform logs
  • clear COMTRADE waveform records from FTP site


Resolution
In order to perform a master reset on the PM8000 follow steps or video below:

  1. Open ION Setup
  2. Connect to the PM8000 meter
  3. Select Setup Assistant
  4. Select Verification
  5. Select Normal Mode or Display as shown below

Setup Assistant in ION Setup

  1. Select Master Reset

Energy values from the meter

The screen shot below shows all the resets available.
Types of resets that can be performed by the meter