Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Why do the Quantum high end CPU Eth Coprocessor and the 140NOE, when they ioscan the same DIO toward %I, end with reversed result
20 years ago, the 2 products were designed differently, one is little endian while the other is big endian.
the customer is advised to always store the ioscan result in %MW instead of %I not to face this issue.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings