Can you land (2) 600 kcmil wire to a PTQ36080G (H, or V) switch?
Issue:
How to wire (2) 600 kcmil to a PTQ36080G (H, or V) switch?

Product Line:
I Line II Busway

Environment:
Installation

Cause:
Options

Resolution:
Yes , since the 1200A and 800A switch enclosures are the same size , wire bending restrictions are not an issue. Using AL800P6K4 lug kit will allow the terminating of (2) 600 kcmil conductors / per phase in the load end of the PTQ switch . The 800A switch normally accepts (3) 500 kcmil with AL800M23K4 lug kit .