Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Video: How do you set a run permissive on an ATV312 drive?

Article available in these languages: Spanish

Issue:
ATV312 how to set up a permissive run

Product Line:
Altivar 312, ATV312

Environment:
All

Cause:
Safety, permissive function.

Resolution:
In the programming, go into menus FUn-, StC-, and parameter nSt.  Assign nSt to a logic input LIx to act as a permissive.
If that corresponding logic input does not have a +24VDC applied, the drive will show nSt on the display to indicate freewheel stop status.
The freewheel stop / run permissive function applies for both Local and Remote modes of operation.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings