Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What can cause a CF12 fault [Download transfer fault] on an ATV212 drive?
Issue:
CF12 fault [Download transfer fault] on an ATV212 drive.

Environment:
All models and serial numbers

Cause:
The download transfer fault can be caused by parameter F807 not being set to 0.

Resolution:
Parameter F807 selects the communication channel.  The two choices are 0 [RJ45] and 1 [Open style].  The default setting is 1.  If SoMove or the IPAD app is being used to configure the drive parameter F807, then it must be set to 0.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings