Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What would cause ground leakage current on an ATV61 or ATV71?
Issue:
What is the Ground leakage current for SCF3 fault?

Product Line:
Altivar 61, Altivar 71

Environment:
All

Cause:
Drive is tripping on SCF3 fault.

Resolution:
The threshold for a SCF3 fault (short-circuit to Ground) is 25% of drive nominal current. It is a hardware detection and it is not adjustable.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings