Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Do we need to install Vijeo Designer Runtime to download to a Magelis HMI?
Issue:
It is unclear what the Vijeo Designer Runtime for Windows package is intended for.

Product Range:
Vijeo Designer 5.1 or higher

Resolution:
The Vijeo Designer Runtime for Windows executable does not need to be installed to download to a Magelis HMI. This installer is only intended to be used on iPCs or PCs that will be used as an HMI. You do not need to install this package on the Vijeo Designer development PC.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings