Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Unity Pro : Use of operation on index in INC or DEC function causes a Build error
Goals and Symptoms

When building an application using operation on index in INC or DEC function the build fails with following error message : error during the ARM assembler phase
Code generation failure

Example:  INC(my_array[ind*3+1]);

The problem is in Unity Pro V8.0 to V11.0.

Causes and Fixes:
The workaround consits to program the operation outside the function.

Example :
Ind1 :=ind*3+1 ;INC(my_array[ind1]);

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings