Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the StUn parameter for the ATV32 Drive?
Issue:
Customer was asked to change StUn to CUS per the machine OEM, but he is unable to change this value

Product line:
Altivar 32, ATV32

Environment:
all

Cause:
n/a

Resolution:
The StUn parameter for Tune Selection is a Read only parameter, found in the drC menu.

The factory setting is tAb (Default).
If an autotune is completed, this value changes to MEAS (Measured).
To change this value to CUS (Custom) the motor measurements must be manually entered and saved.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings